Allen-Bradley 1763-L16AWA MicroLogix 16-point – Pickup in Store
In stock: 1 unit in Milwaukee, WI. Physically stocked and ready to ship or available for local pickup. Includes a 1-year full-function warranty.
MicroLogix 1100 controller · 10 × 120V AC inputs · 6 relay outputs · 2 analog inputs (0…10V) · 120/240V AC powered

Actual NJT inventory photos
Price
$1,049.99USDUsed, Series BView listing
| Part Number | 1763-L16AWA |
| Description | MicroLogix 1100 controller, 16-point, 120/240V AC. In stock in used condition, Series B. |
| Shipping | Ships same or next business day
|
| Pickup | Free local pickup at 2122 N Prospect Ave. Call ahead at (414) 331-5954. |
| Warranty | 1-year full-function warranty provided by NJT Automation. Warranty details
|
| Returns | 90-day free returns. View return policy |
| Exchange | Send us your defective 1763-L16AWA after your purchase for a 10% core credit. We also purchase old or damaged parts outright. |
Replacement Options for 1763-L16AWA
| Variants | Part NumberConditionSeriesQtyPrice 1763-L16AWA /B$1,049.99 Used · Series B · 1 in stock1763-L16AWA /BUsedSeries B1$1,049.99 USD | ||||||||
| Availability | 1 unit in stock | ||||||||
| Repairs | 1763-L16AWA Mail-In Repair ServiceEstimated: $1,440.00 | ||||||||
Part Number Decoder | MicroLogix 1100 controller 1763L16AWA
Decoded from the Rockwell Automation catalog-number structure. Series and firmware revision are printed on the product label, not encoded here. | ||||||||
Series & Revisions | Series B in stock; other series on request. Series notes: A later series runs the existing program after the processor type is changed in RSLogix 500. An earlier series may not if the program uses features from a newer OS/FRN. | ||||||||
Intended Use | Built for Ethernet-connected small machine control applications. MicroLogix 1100 controllers handle compact machines, pump and fan sequencing, small conveyors and monitoring panels where built-in Ethernet and a front LCD are wanted at a low point count. | ||||||||
Physical Data | Weight and DimensionsWeight1.98 lb (0.90 kg)H × W × D3.5 × 4.3 × 3.4 in. (90 × 110 × 87 mm)
Product weight and dimensions are typical manufacturer-published values and may differ by series or option. Shipping box and weight are estimates for freight planning; the packed unit may ship in a different box. | ||||||||
Similar Part Numbers |
| ||||||||
Allen Bradley Information | Technical SpecificationsLifecycle status
| ||||||||
| Category | MicroLogix | ||||||||
| UPC / GTIN | 662074023028 | ||||||||
| Part Number | 1763-L16AWA | ||||||||
| Manufacturer | Allen-Bradley | ||||||||
Previously sold 1763-L16AWA1 sold
NJT Automation has supplied and shipped one 1763-L16AWA MicroLogix 1100 controller in 2026; these listings are sold and the in-stock options above are ready to ship.
- Sold
- 1 in 2026
- Series
- B × 1
Image gallery21 PHOTOSActual units photographed by NJT
Can the 1763-L16AWA be repaired?
Yes. NJT Automation repairs the 1763-L16AWA by mail-in: diagnostic evaluation, component-level repair and a functional test, backed by a 1-year full-function warranty.
Option 1
NJT managed repair
- Evaluation
- Free. No repair, no charge.
- Shipping
- Prepaid UPS label both ways.
- Pricing
- $650 minimum. Rush service available.
- Warranty
- 1-year full-function warranty included; 2- and 3-year options.
Option 2
Independent repair bids. Compare quotes from independent repair technicians. Post your repair on RepairMode to receive competitive bids from experienced technicians. Each technician sets their own pricing and warranty.
Common Failures
Failure patterns we regularly see on MicroLogix 1100 controller hardware like the 1763-L16AWA:
- Embedded Ethernet port dead or dropping connections
- LCD blank, garbled or unresponsive keypad
- Output relays welded or burned on high-cycle machines (-BWA / -AWA)
- Channel 0 RS-232 / RS-485 port damaged by a hot-plugged cable
- Program lost after a power event
Fault code reference
1763-L16AWA Fault Codes
44 codes · 1763-RM001
Fault codes a MicroLogix 1100 controller reports on the controller LCD and status word S:6 in RSLogix 500 / RSLogix Micro (hexadecimal), as documented in Rockwell Automation publication 1763-RM001. Use them to narrow a problem down to the unit, its wiring or the application before sending it in for repair.
| Code | Fault | What it indicates |
|---|---|---|
| 0001 | NVRAM error | Program memory was corrupted (power loss during download, noise, failing battery) and the default program was loaded. |
| 0002 | Unexpected reset | The controller reset unexpectedly due to noise or an internal hardware failure; the default program is loaded. |
| 0003 | Memory module program corrupt | Memory module memory error; can also appear when going to Run mode. |
| 0004 | Memory integrity error | ROM or RAM became corrupt at power-up or during the background integrity check. |
| 0006 | Memory module hardware fault | The memory module hardware faulted or is incompatible with the operating system. |
| 0007 | Memory module transfer error | Failure during memory module transfer. |
| 0008 | Fatal internal software error | Unexpected software error; cycle power and reload the program. |
| 0009 | Fatal internal hardware error | Unexpected hardware error; cycle power and reload the program. |
| 000A | OS missing or corrupt | The operating system required for the user program is missing or corrupt. |
| 000B | Base hardware fault | The base hardware faulted or is incompatible with the operating system. |
Show 34 more codes
| 0011 | Executable file 2 missing | Ladder file 2 is missing from the program. |
| 0012 | Ladder program error | The ladder program has a memory integrity problem. |
| 0015 | I/O configuration file error | The user program I/O configuration is invalid. |
| 0016 | Startup protection fault | The user fault routine ran at power-up and S:1/13 was not cleared. |
| 0017 | NVRAM / memory module mismatch | S:2/9 is set and the memory module program does not match the controller program. |
| 0018 | Memory module program incompatible with OS | The program stored in the memory module needs a newer operating system. |
| 001A | User program incompatible with OS | The user program is incompatible with the controller operating system. |
| 0020 | Minor error at end of scan | A minor fault bit (S:5 bits 0–7) was set at the end of the scan. |
| 0022 | Watchdog timer expired | The program scan time exceeded the watchdog timeout in S:3H. |
| 0023 | STI error | An error occurred in the STI configuration; see the STI function file. |
| 0028 | Invalid user fault routine | The fault routine number in S:29 is invalid or the routine does not exist. |
| 0029 | Indirect address outside data space | An indirect address reference is outside the entire data file space. |
| 002E | EII error | An error occurred in the EII configuration; see the EII function file. |
| 0030 | Subroutine nesting exceeds limit | JSR nesting exceeded the controller memory space. |
| 0031 | Unsupported instruction | The program contains an instruction this controller does not support. |
| 0032 | Sequencer outside data file space | An SQO / SQC / SQL length or position parameter references outside the data file space. |
| 0033 | Bit shift / FIFO / LIFO crossed data file | A BSL, BSR, FFL, FFU, LFL or LFU parameter references outside the data file space. |
| 0034 | Negative timer value | A negative value was loaded to a timer preset or accumulator. |
| 0035 | Illegal instruction in interrupt file | A TND, REF or SVC instruction is used in an interrupt subroutine. |
| 0036 | Invalid PID parameter | An invalid value is being used for a PID instruction parameter. |
| 0037 | HSC error | An error occurred in the high-speed counter configuration; see the HSC function file. |
| 003B | PTO error | An error occurred in the PTO instruction configuration. |
| 003C | PWM error | An error occurred in the PWM instruction configuration. |
| 003D | Invalid sequencer length / position | A sequencer length or position parameter is greater than 255. |
| 003E | Invalid bit shift or FIFO / LIFO parameter | A BSR / BSL length is greater than 2048, or an FFU / FFL / LFU / LFL length is out of range. |
| 003F | COP / CPW / FLL outside data file space | A COP, CPW or FLL length parameter references outside the data space. |
| 0042 | Invalid recipe number | Number of recipes specified is greater than 256. |
| 0044 | Invalid write to RTC function file | A write to the real-time clock function file contained invalid data. |
| 0050 | Controller type mismatch | The controller type selected in the program does not match the actual controller. |
| 0051 | Base type mismatch | The hardware base type selected in the program does not match the actual base. |
| 0052 | Minimum series error | The hardware minimum series in the program is newer than the actual hardware. |
| 0083 | Max I/O cables exceeded | Too many expansion I/O cables in the system. |
| 0084 | Max I/O power supplies exceeded | Too many expansion I/O power supplies in the system. |
| 0085 | Max I/O modules exceeded | Too many expansion I/O modules in the system. |
Where the manual's only remedy for a code is to replace the unit or module, the code is pointing at a hardware fault inside that part. Those are the faults NJT Automation repairs at component level, so a repair quote is usually the first thing to check before buying a replacement.
Source: Rockwell Automation publication 1763-RM001, MicroLogix 1100 Programmable Controllers Instruction Set Reference Manual. Codes are listed as documented; fault behaviour can vary by firmware revision, so confirm against the manual for your unit's series.
Photos by NJT Automation; test videos from NJT or network repair technicians.
Still have questions?
Find answers to shipping, warranties, repairs, and more.