Allen-Bradley 1763 · Fault code reference

MicroLogix 1100 Fault Codes

Every fault code a MicroLogix 1100 reports on the controller LCD and status word S:6 in RSLogix 500 / RSLogix Micro (hexadecimal), with what each one indicates, as documented in Rockwell Automation publication 1763-RM001.

44 codes · 1763-RM001 · 29 part numbers covered

MicroLogix 1100 fault code list

MicroLogix 1100 fault codes
CodeFaultWhat it indicates
0001NVRAM errorProgram memory was corrupted (power loss during download, noise, failing battery) and the default program was loaded.
0002Unexpected resetThe controller reset unexpectedly due to noise or an internal hardware failure; the default program is loaded.
0003Memory module program corruptMemory module memory error; can also appear when going to Run mode.
0004Memory integrity errorROM or RAM became corrupt at power-up or during the background integrity check.
0006Memory module hardware faultThe memory module hardware faulted or is incompatible with the operating system.
0007Memory module transfer errorFailure during memory module transfer.
0008Fatal internal software errorUnexpected software error; cycle power and reload the program.
0009Fatal internal hardware errorUnexpected hardware error; cycle power and reload the program.
000AOS missing or corruptThe operating system required for the user program is missing or corrupt.
000BBase hardware faultThe base hardware faulted or is incompatible with the operating system.
0011Executable file 2 missingLadder file 2 is missing from the program.
0012Ladder program errorThe ladder program has a memory integrity problem.
0015I/O configuration file errorThe user program I/O configuration is invalid.
0016Startup protection faultThe user fault routine ran at power-up and S:1/13 was not cleared.
0017NVRAM / memory module mismatchS:2/9 is set and the memory module program does not match the controller program.
0018Memory module program incompatible with OSThe program stored in the memory module needs a newer operating system.
001AUser program incompatible with OSThe user program is incompatible with the controller operating system.
0020Minor error at end of scanA minor fault bit (S:5 bits 0–7) was set at the end of the scan.
0022Watchdog timer expiredThe program scan time exceeded the watchdog timeout in S:3H.
0023STI errorAn error occurred in the STI configuration; see the STI function file.
0028Invalid user fault routineThe fault routine number in S:29 is invalid or the routine does not exist.
0029Indirect address outside data spaceAn indirect address reference is outside the entire data file space.
002EEII errorAn error occurred in the EII configuration; see the EII function file.
0030Subroutine nesting exceeds limitJSR nesting exceeded the controller memory space.
0031Unsupported instructionThe program contains an instruction this controller does not support.
0032Sequencer outside data file spaceAn SQO / SQC / SQL length or position parameter references outside the data file space.
0033Bit shift / FIFO / LIFO crossed data fileA BSL, BSR, FFL, FFU, LFL or LFU parameter references outside the data file space.
0034Negative timer valueA negative value was loaded to a timer preset or accumulator.
0035Illegal instruction in interrupt fileA TND, REF or SVC instruction is used in an interrupt subroutine.
0036Invalid PID parameterAn invalid value is being used for a PID instruction parameter.
0037HSC errorAn error occurred in the high-speed counter configuration; see the HSC function file.
003BPTO errorAn error occurred in the PTO instruction configuration.
003CPWM errorAn error occurred in the PWM instruction configuration.
003DInvalid sequencer length / positionA sequencer length or position parameter is greater than 255.
003EInvalid bit shift or FIFO / LIFO parameterA BSR / BSL length is greater than 2048, or an FFU / FFL / LFU / LFL length is out of range.
003FCOP / CPW / FLL outside data file spaceA COP, CPW or FLL length parameter references outside the data space.
0042Invalid recipe numberNumber of recipes specified is greater than 256.
0044Invalid write to RTC function fileA write to the real-time clock function file contained invalid data.
0050Controller type mismatchThe controller type selected in the program does not match the actual controller.
0051Base type mismatchThe hardware base type selected in the program does not match the actual base.
0052Minimum series errorThe hardware minimum series in the program is newer than the actual hardware.
0083Max I/O cables exceededToo many expansion I/O cables in the system.
0084Max I/O power supplies exceededToo many expansion I/O power supplies in the system.
0085Max I/O modules exceededToo many expansion I/O modules in the system.

Is it a hardware fault?

Where the manual's only remedy for a code is to replace the unit or module, the code is pointing at a hardware fault inside that part, not at wiring, configuration or the application. Those are the faults NJT Automation repairs at component level. A repair is usually cheaper and faster than a replacement for an obsolete MicroLogix 1100 unit; each part number below links to its stock, repair pricing and test videos.

Faults are read from the controller LCD and status word S:6 in RSLogix 500 / RSLogix Micro (hexadecimal).

Source

Codes are listed as documented. Fault behaviour can vary by firmware revision, so confirm against the manual for your unit's series. Spotted an error? Tell us and we will correct it.

Related references

MicroLogix 1100 part numbers these codes apply to

29 catalog numbers, 2 in stock now. Each links to stock, condition, repair pricing and series notes for that catalog number.

Disclaimer

Trademarks & Compatibility

All trademarks, service marks, trade names, brand names, and logos displayed on this website are the property of their respective owners. Any references to manufacturers, products, or brands are for identification and compatibility purposes only and do not imply any affiliation with, endorsement by, sponsorship from, or authorization by the respective trademark owners.

Independent Supplier

NJT Automation is an independent supplier of surplus, refurbished, and pre-owned industrial automation equipment. Unless expressly stated otherwise, NJT Automation is not an authorized distributor, dealer, representative, or affiliate of the original equipment manufacturer (OEM) for any products offered on this website.

Product Condition & Warranty

Products sold by NJT Automation may be surplus inventory, discontinued models, older series, or units with earlier manufacturing date codes than those currently available from the OEM or its authorized distribution network. As NJT Automation is not an authorized distributor, manufacturer warranties, support programs, and other OEM services may not apply. Any warranty provided is solely that of NJT Automation, where applicable.

Firmware & Software Licensing

Certain programmable logic controllers (PLCs), drives, HMIs, and other electronic products may require firmware to operate. While some products may include firmware, NJT Automation makes no representations or warranties regarding whether firmware is installed, the firmware version or revision level, its compatibility with your application, or its licensing status.

NJT Automation does not provide, obtain, transfer, or license firmware on behalf of customers. We make no representation regarding your ability or legal right to obtain, download, install, or use firmware from the OEM, its authorized distributors, or any other source. It is the customer's sole responsibility to ensure compliance with all applicable End User License Agreements (EULAs), software licenses, intellectual property rights, and other terms governing the acquisition, installation, and use of firmware.