NJT Automation has supplied and shipped one 2711PC-T10C4D1 PanelView Plus Compact touch terminal in 2025; these listings are sold and the in-stock options above are ready to ship.
- Sold
- 1 in 2025
- Series
- A × 1
In stock: 1 unit in Milwaukee, WI.
PanelView Plus Compact 10.4-in. color touch terminal · Ethernet + RS-232 · 24V DC powered

Actual NJT inventory photos
Price
$3,349.99USDUnused surplus (open box)View listing
| Part Number | 2711PC-T10C4D1 |
| Description | PanelView Plus Compact touch terminal, 10.4-in. Touch, 24V DC. In stock in unused surplus condition. |
| Shipping | Ships same or next business day
|
| Pickup | Free local pickup at 2122 N Prospect Ave. Call ahead at (414) 331-5954. |
| Warranty | 1-year full-function warranty provided by NJT Automation. Warranty details
|
| Returns | 90-day free returns. View return policy |
| Exchange | Send in your defective 2711PC-T10C4D1 for a 10% core credit. |
| Variants | Part NumberConditionSeriesQtyPrice 2711PC-T10C4D1$3,349.99 Unused surplus (open box) · 1 in stock2711PC-T10C4D1Unused surplus (open box)—1$3,349.99 USD | ||||||||
| Availability | 1 Unit in StockIndependently SourcedNot an OEM-Authorized Distributor | ||||||||
| Repairs | 2711PC-T10C4D1 Mail-In Repair Service | ||||||||
Part Number Decoder | PanelView Plus Compact touch terminal 2711PC·T·10·C·4·D·1
Decoded from the Rockwell Automation catalog-number structure. Series and firmware revision are printed on the product label, not encoded here. | ||||||||
Series & Revisions | No series in stock today; request a series above. Series notes: Same cutout and connections across series; confirm the replacement's firmware supports the project's FactoryTalk View ME version. | ||||||||
Intended Use | Designed for standalone machine operator interface applications. PanelView Plus Compact terminals run a single-controller FactoryTalk View ME application on OEM machines and small cells where a full PanelView Plus is more than the job needs. | ||||||||
Physical Data | Weight and DimensionsWeight6.39 lb (2.90 kg)H × W × D9.8 × 13 × 2.2 in. (248 × 329 × 55 mm)▾
Product weight and dimensions are typical manufacturer-published values and may differ by series or option. Shipping box and weight are estimates for freight planning; the packed unit may ship in a different box. | ||||||||
| Category | PanelView Plus | ||||||||
| UPC / GTIN | 612598766086 | ||||||||
| Part Number | 2711PC-T10C4D1 | ||||||||
| Manufacturer | Allen-Bradley | ||||||||
NJT Automation has supplied and shipped one 2711PC-T10C4D1 PanelView Plus Compact touch terminal in 2025; these listings are sold and the in-stock options above are ready to ship.
Yes. NJT Automation repairs the 2711PC-T10C4D1 by mail-in: diagnostic evaluation, component-level repair and a functional test.
Option 1
NJT Managed Repair
Option 2
Independent repair bids. Compare quotes from independent repair technicians. Post your repair on RepairMode to receive competitive bids from experienced technicians. Each technician sets their own pricing and warranty.
Failure patterns we regularly see on PanelView Plus Compact touch terminal hardware like the 2711PC-T10C4D1:
Fault code reference
Fault codes a PanelView Plus Compact touch terminal reports on the screen at start-up (error number with an ERROR! message) and the Fault (red) and Comm (green) indicators, as documented in Rockwell Automation publication 2711P-UM001. Use them to narrow a problem down to the unit, its wiring or the application before sending it in for repair.
| Error # | Displayed message | What it indicates |
|---|---|---|
| 1 | RAM Test | RAM test failure. Reset the terminal; if it persists, reseat the SO-DIMM (700…1500). A persistent failure is a logic board fault. |
| 14 | RAM Header Check | The OS firmware being downloaded is not compatible with the hardware (400/600 terminals). |
| 20 | Transfer Image | Programming the downloaded OS firmware into flash failed (400/600 terminals). |
| 23 | Download Task / Internal CF | Firmware image too large (400/600), or an error programming firmware to the internal CompactFlash (700…1500). |
| 24 | CRC Check | Checksum of the OS firmware failed; reload firmware. Persistent failures point to the internal CompactFlash or logic module. |
| 25 | Invalid Prod Family | The OS firmware being downloaded is not for this terminal family (400/600 terminals). |
| 27 | Decompress System | Error decompressing the OS firmware from flash to RAM (400/600 terminals). |
| 30 | Watchdog Test | Watchdog test failure; reload firmware, then suspect the logic module. |
| 31 | Stuck Key | A function key is held or stuck. Make sure nothing presses on the keypad (on the 400/600, tap F1 rather than holding it to enter Configuration mode) and reset; persistent failures mean the keypad / display module. |
| 31.5 | Stuck Touch | Touch screen reports a constant touch (700…1500 terminals). Remove anything pressing on the screen, including a damaged anti-glare overlay, and reset; persistent failures mean the display module. |
| 32 | Battery Test | Battery failure (700…1500 terminals). Fit a new battery; if it persists, the fault is on the logic module. |
| 33.5 | NVRAM Access | Nonvolatile memory failure (700…1500 terminals); upgrade system firmware to 3.10.03 or later. |
| 3a | Stuck Touch | Touch screen reports a constant touch (400/600 terminals). Remove anything pressing on the screen, including a damaged anti-glare overlay, and reset; persistent failures mean the terminal. |
| 40 | EXE Check | System OS firmware is missing or corrupt; reload firmware. |
| 50 | External CF | Error loading OS firmware from the external CompactFlash card. |
| Indicators | State | What it indicates |
|---|---|---|
| Fault blinking · Comm off | Last firmware download failed | Recoverable: reload the firmware with the Firmware Upgrade Wizard. |
| Fault blinking · Comm blinking | Boot loader firmware failed or missing | Recoverable: reload the firmware with the Firmware Upgrade Wizard. |
| Fault blinking · Comm on | Windows CE OS firmware failed or missing | Recoverable: reload the firmware with the Firmware Upgrade Wizard. |
| Fault on · Comm off | Fatal hardware error | Hardware fault in the logic module (700…1500) or the terminal's logic board (400/600). |
| Fault on · Comm blinking | Fatal hardware error in display | Hardware fault in the display module (700…1500) or the terminal's display section (400/600). |
Where the manual's only remedy for a code is to replace the unit or module, the code is pointing at a hardware fault inside that part. Those are the faults NJT Automation repairs at component level, so a repair quote is usually the first thing to check before buying a replacement.
Source: Rockwell Automation publication 2711P-UM001, PanelView Plus Terminals User Manual. Codes are listed as documented; fault behaviour can vary by firmware revision, so confirm against the manual for your unit's series.
PanelView Plus fault code reference · every code and every part number it covers
Photos by NJT Automation; test videos from NJT or network repair technicians.
Find answers to shipping, warranties, repairs, and more.
Trademarks & Compatibility
All trademarks, service marks, trade names, brand names, and logos displayed on this website are the property of their respective owners. Any references to manufacturers, products, or brands are for identification and compatibility purposes only and do not imply any affiliation with, endorsement by, sponsorship from, or authorization by the respective trademark owners.
Independent Supplier
NJT Automation is an independent supplier of surplus, refurbished, and pre-owned industrial automation equipment. Unless expressly stated otherwise, NJT Automation is not an authorized distributor, dealer, representative, or affiliate of the original equipment manufacturer (OEM) for any products offered on this website.
Product Condition & Warranty
Products sold by NJT Automation may be surplus inventory, discontinued models, older series, or units with earlier manufacturing date codes than those currently available from the OEM or its authorized distribution network. As NJT Automation is not an authorized distributor, manufacturer warranties, support programs, and other OEM services may not apply. Any warranty provided is solely that of NJT Automation, where applicable.
Firmware & Software Licensing
Certain programmable logic controllers (PLCs), drives, HMIs, and other electronic products may require firmware to operate. While some products may include firmware, NJT Automation makes no representations or warranties regarding whether firmware is installed, the firmware version or revision level, its compatibility with your application, or its licensing status.
NJT Automation does not provide, obtain, transfer, or license firmware on behalf of customers. We make no representation regarding your ability or legal right to obtain, download, install, or use firmware from the OEM, its authorized distributors, or any other source. It is the customer's sole responsibility to ensure compliance with all applicable End User License Agreements (EULAs), software licenses, intellectual property rights, and other terms governing the acquisition, installation, and use of firmware.
© 2026 NJT Automation. Independent industrial automation supplier and repair provider.