PowerFlex 753 and 755 Fault Codes

Every fault code a PowerFlex 753 and 755 reports on the HIM fault queue (fault number and text) and the drive's fault status parameters, with what each one indicates, as documented in Rockwell Automation publication 750-PM001.

54 codes · 750-PM001 · 326 part numbers covered

PowerFlex 753 and 755 fault code list

PowerFlex 753 and 755 fault codes
CodeFaultWhat it indicates
2Auxiliary InputAn auxiliary input interlock is open; the application is not allowing the drive to energize.
3Power LossDC bus voltage stayed below the power-loss level for longer than the programmed time.
4UnderVoltageDC bus voltage fell below the undervoltage level.
5OverVoltageDC bus voltage exceeded the maximum value.
7Motor OverloadInternal electronic motor overload trip.
8Heatsink OvrTempHeatsink temperature exceeded 100% of the drive temperature rating.
9Trnsistr OvrTempThe output transistors exceeded their maximum operating temperature.
12HW OverCurrentOutput current exceeded the hardware current limit: grounded or shorted motor leads.
13Ground FaultA current path to earth ground greater than 25% of drive rating occurred.
14Ground WarningGround current exceeded the programmed warning level.
15Load LossOutput torque current fell below the load-loss level for longer than the programmed time.
17Input Phase LossDC bus ripple exceeded a preset level: check input impedance, phases and fuses.
20TorqPrv Spd BandCommanded speed and motor velocity feedback differ by more than the speed deviation band.
21Output PhaseLossCurrent in one or more output phases was lost or stayed below the threshold.
24Decel InhibitThe drive is not following the commanded deceleration because it is limiting bus voltage.
25OverSpeed LimitMotor speed exceeded the overspeed limit.
33AuRsts ExhaustedThe drive used all programmed auto-restart tries without clearing the fault.
35IPM OverCurrentCurrent magnitude exceeded the IPM trip level.
36SW OverCurrentOutput current exceeded the 1 ms current rating.
38 / 39 / 40Phase U / V / W to GrndA phase-to-ground fault was detected between the drive and motor in that phase.
41 / 42 / 43Phase UV / VW / WU ShortExcessive current was detected between two output terminals.
48System DefaultedThe drive was commanded to write default values.
55Ctrl Bd OvertempThe main control board temperature sensor detected excessive heat.
59Invalid CodeInternal error.
61 / 62Shear Pin 1 / 2The programmed shear-pin torque level was exceeded.
64Drive OverLoadThe drive overload count exceeded 100%.
71–76Port 1–6 AdapterThe DPI communications option on that port has a fault.
77IR Volts RangeThe IR voltage drop calculated from motor nameplate data is out of range.
78FluxAmpsRef RangFlux amps exceed the motor nameplate amps as calculated by autotune.
79Excessive LoadThe motor did not come up to speed in the allotted time during autotune.
80AutoTune AbortedThe autotune function was cancelled or a fault occurred.
81–86Port 1–6 DPI LossThe DPI port stopped communicating.
91Pri VelFdbk LossFeedback loss detected for the primary velocity feedback source.
93Hw Enable CheckThe hardware enable is jumpered out but indicates not enabled.
94Alt VelFdbk LossFeedback loss detected for the alternate velocity feedback source.
96PositionFdbkLossFeedback loss detected for the position feedback source.
100Parameter ChksumThe parameter checksum read from non-volatile storage does not match.
104Pwr Brd ChecksumThe power board checksum does not match; data is set to default values.
106Incompat MCB PBThe main control board did not recognize the power structure; flash newer firmware.
107Replaced MCB PBThe main control board was moved to another power structure; data is set to defaults.
108Anlg Cal ChksumThe analog calibration checksum does not match; a fault on the main control board.
110Ivld Pwr Bd DataPower structure data invalid; check the ribbon cable between the control and power interface boards.
111PwrBd Invalid IDPower structure ID invalid; check the ribbon cable between the control and power interface boards.
112PwrBd App MinVerThe power structure needs a newer application firmware revision.
124App ID ChangedApplication firmware changed; verify the application revision.
125Using Backup AppThe application did not flash correctly; reflash.
137Ext Prechrg ErrThe seal contact on the external precharge contactor opened.
138Precharge OpenThe internal precharge contactor is open.
141Autn Enc AngleEncoderless angle compensation is out of range after autotune.
142Autn Spd RstrctFrequency limit settings prevented a suitable autotune speed.
143Autotune CurRegCalculated current-regulator gains are out of range.
144Autotune InertiaInertia test results are out of range.
145Autotune TravelThe inertia test was prevented from reaching the required speed within the travel limit.
152No Stop SourceThe last stop source was removed.

Is it a hardware fault?

Where the manual's only remedy for a code is to replace the unit or module, the code is pointing at a hardware fault inside that part, not at wiring, configuration or the application. Those are the faults NJT Automation repairs at component level. A repair is usually cheaper and faster than a replacement for an obsolete PowerFlex 753 and 755 unit; each part number below links to its stock, repair pricing and test videos.

Faults are read from the HIM fault queue (fault number and text) and the drive's fault status parameters.

Source

Codes are listed as documented. Fault behaviour can vary by firmware revision, so confirm against the manual for your unit's series. Spotted an error? Tell us and we will correct it.

Related references

PowerFlex 753 and 755 part numbers these codes apply to

326 catalog numbers, 11 in stock now. Each links to stock, condition, repair pricing and series notes for that catalog number.

Disclaimer

Trademarks & Compatibility

All trademarks, service marks, trade names, brand names, and logos displayed on this website are the property of their respective owners. Any references to manufacturers, products, or brands are for identification and compatibility purposes only and do not imply any affiliation with, endorsement by, sponsorship from, or authorization by the respective trademark owners.

Independent Supplier

NJT Automation is an independent supplier of surplus, refurbished, and pre-owned industrial automation equipment. Unless expressly stated otherwise, NJT Automation is not an authorized distributor, dealer, representative, or affiliate of the original equipment manufacturer (OEM) for any products offered on this website.

Product Condition & Warranty

Products sold by NJT Automation may be surplus inventory, discontinued models, older series, or units with earlier manufacturing date codes than those currently available from the OEM or its authorized distribution network. As NJT Automation is not an authorized distributor, manufacturer warranties, support programs, and other OEM services may not apply. Any warranty provided is solely that of NJT Automation, where applicable.

Firmware & Software Licensing

Certain programmable logic controllers (PLCs), drives, HMIs, and other electronic products may require firmware to operate. While some products may include firmware, NJT Automation makes no representations or warranties regarding whether firmware is installed, the firmware version or revision level, its compatibility with your application, or its licensing status.

NJT Automation does not provide, obtain, transfer, or license firmware on behalf of customers. We make no representation regarding your ability or legal right to obtain, download, install, or use firmware from the OEM, its authorized distributors, or any other source. It is the customer's sole responsibility to ensure compliance with all applicable End User License Agreements (EULAs), software licenses, intellectual property rights, and other terms governing the acquisition, installation, and use of firmware.