CodeFaultWhat it indicates
F002Auxiliary InputThe auxiliary input interlock is open.
F003Power LossExcessive DC bus voltage ripple: incoming phase loss, line imbalance or a blown input fuse.
F004UnderVoltageDC bus voltage fell below the minimum value: low or interrupted incoming line.
F005OverVoltageDC bus voltage exceeded the maximum value: high line, transients or regenerative load with too short a decel time.
F006Motor StalledThe drive is unable to accelerate or decelerate the motor.
F007Motor OverloadInternal electronic motor overload trip.
F008Heatsink OvrTmpHeatsink temperature exceeded the limit: blocked or dirty fins, high ambient or a failed fan.
F009CC OvrTmpControl module temperature exceeded the limit.
F012HW OverCurrentOutput current exceeded the hardware current limit: shorted or grounded motor leads, or a failed power stage.
F013Ground FaultA current path to earth ground was detected at one or more output terminals.
F015Load LossOutput torque current fell below the programmed load-loss level.
F021Output Ph LossOutput phase loss detected (when enabled).
F029Analog In LossAn analog input configured to fault on signal loss has lost its signal.
F033Auto Rstrt TriesThe drive used all programmed auto-restart attempts without clearing the fault.
F038 / F039 / F040Phase U / V / W to GndA phase-to-ground fault was detected between the drive and motor in that phase.
F041 / F042 / F043Phase UV / UW / VW ShortExcessive current was detected between two output terminals.
F048Params DefaultedThe drive was commanded to write default values to EEPROM.
F059Safety OpenBoth safety inputs (Safety 1, Safety 2) are not enabled.
F063SW OverCurrentThe programmed software current trip level was exceeded.
F064Drive OverloadThe drive rating of 150% for 1 minute or 200% for 3 seconds was exceeded.
F070Power UnitA failure was detected in the drive power section.
F071DSI Net LossThe DSI communication network faulted.
F072Opt Net LossThe option-card network faulted.
F073EN Net LossControl through the embedded EtherNet/IP adapter was interrupted.
F080Autotune FailureThe autotune function was cancelled or failed.
F081DSI Comm LossThe RS-485 (DSI) port stopped communicating.
F082Opt Comm LossCommunication with the option card was lost.
F083EN Comm LossCommunication with the embedded EtherNet/IP adapter was lost.
F091Encoder LossEncoder feedback was lost (encoder option card).
F094Function LossThe function-loss input is open.
F100Parameter ChksumThe parameter checksum does not match: reset to defaults and reprogram.
F101External StorageExternal (keypad / USB) storage read or write failed.
F105C Connect ErrThe control module was disconnected from the power module while powered.
F106Incompat C-PThe control module firmware is incompatible with the power module.
F107Replaced C-PThe control module was moved to a different power module; parameters were defaulted.
F109Mismatch C-PThe control module and power module ratings do not match.
F110Keypad MembraneThe keypad membrane failed or a key is stuck.
F111Safety HardwareThe safety input hardware failed.
F114uC FailureMicrocontroller failure.
F122I/O Board FailA failure was detected in the drive control and I/O section.
F125Flash Update ReqA firmware flash update is required.
F126NonRecoverablErrA non-recoverable error occurred.
F127DSIFlashUpdatReqA DSI firmware flash update is required.

Is it a hardware fault?

Where the manual's only remedy for a code is to replace the unit or module, the code is pointing at a hardware fault inside that part, not at wiring, configuration or the application. Those are the faults NJT Automation repairs at component level. A repair is usually cheaper and faster than a replacement for an obsolete PowerFlex 523 and 525 unit; each part number below links to its stock, repair pricing and test videos.

Faults are read from the drive's integral keypad display (F followed by the fault number).

Source

Codes are listed as documented. Fault behaviour can vary by firmware revision, so confirm against the manual for your unit's series. Spotted an error? Tell us and we will correct it.

Related references

PowerFlex 523 and 525 part numbers these codes apply to

73 catalog numbers, 5 in stock now. Each links to stock, condition, repair pricing and series notes for that catalog number.

Disclaimer

Trademarks & Compatibility

All trademarks, service marks, trade names, brand names, and logos displayed on this website are the property of their respective owners. Any references to manufacturers, products, or brands are for identification and compatibility purposes only and do not imply any affiliation with, endorsement by, sponsorship from, or authorization by the respective trademark owners.

Independent Supplier

NJT Automation is an independent supplier of surplus, refurbished, and pre-owned industrial automation equipment. Unless expressly stated otherwise, NJT Automation is not an authorized distributor, dealer, representative, or affiliate of the original equipment manufacturer (OEM) for any products offered on this website.

Product Condition & Warranty

Products sold by NJT Automation may be surplus inventory, discontinued models, older series, or units with earlier manufacturing date codes than those currently available from the OEM or its authorized distribution network. As NJT Automation is not an authorized distributor, manufacturer warranties, support programs, and other OEM services may not apply. Any warranty provided is solely that of NJT Automation, where applicable.

Firmware & Software Licensing

Certain programmable logic controllers (PLCs), drives, HMIs, and other electronic products may require firmware to operate. While some products may include firmware, NJT Automation makes no representations or warranties regarding whether firmware is installed, the firmware version or revision level, its compatibility with your application, or its licensing status.

NJT Automation does not provide, obtain, transfer, or license firmware on behalf of customers. We make no representation regarding your ability or legal right to obtain, download, install, or use firmware from the OEM, its authorized distributors, or any other source. It is the customer's sole responsibility to ensure compliance with all applicable End User License Agreements (EULAs), software licenses, intellectual property rights, and other terms governing the acquisition, installation, and use of firmware.