Allen-Bradley 22B · Fault code reference

PowerFlex 40 Fault Codes

Every fault code a PowerFlex 40 reports on the drive's integral keypad display (F followed by the fault number), with what each one indicates, as documented in Rockwell Automation publication 22B-UM001.

22 codes · 22B-UM001 · 29 part numbers covered

PowerFlex 40 fault code list

PowerFlex 40 fault codes
CodeFaultWhat it indicates
F2Auxiliary InputThe auxiliary input interlock is open; check remote wiring.
F3Power LossExcessive DC bus voltage ripple: incoming phase loss, line imbalance or a blown input fuse.
F4UnderVoltageDC bus voltage fell below the minimum value: low or interrupted incoming line.
F5OverVoltageDC bus voltage exceeded the maximum value: high line, transients or a regenerative load.
F6Motor StalledThe drive is unable to accelerate the motor; lengthen accel time or reduce load.
F7Motor OverloadInternal electronic motor overload trip.
F8Heatsink OvrTmpHeatsink temperature exceeded the limit: blocked or dirty fins, high ambient or a failed fan.
F12HW OverCurrentOutput current exceeded the hardware current limit: excess load, boost setting or shorted motor leads.
F13Ground FaultA current path to earth ground was detected at one or more output terminals.
F29Analog Input LossAn analog input configured to fault on signal loss has lost its signal.
F33Auto Rstrt TriesThe drive used all programmed auto-restart attempts without clearing the fault.
F38 / F39 / F40Phase U / V / W to GndA phase-to-ground fault was detected between the drive and motor in that phase.
F41 / F42 / F43Phase UV / UW / VW ShortExcessive current was detected between two output terminals.
F48Params DefaultedThe drive was commanded to write default values to EEPROM.
F63SW OverCurrentThe programmed software current trip level was exceeded.
F64Drive OverloadThe drive rating of 150% for 1 minute or 200% for 3 seconds was exceeded.
F70Power UnitA failure was detected in the drive power section.
F71Net LossThe communication network faulted; check cabling and adapter settings.
F80SVC AutotuneThe autotune function was cancelled or failed.
F81Comm LossThe RS-485 (DSI) port stopped communicating.
F100Parameter ChecksumThe parameter checksum does not match: reset to defaults and reprogram.
F122I/O Board FailA failure was detected in the drive control and I/O section.

Is it a hardware fault?

Where the manual's only remedy for a code is to replace the unit or module, the code is pointing at a hardware fault inside that part, not at wiring, configuration or the application. Those are the faults NJT Automation repairs at component level. A repair is usually cheaper and faster than a replacement for an obsolete PowerFlex 40 unit; each part number below links to its stock, repair pricing and test videos.

Faults are read from the drive's integral keypad display (F followed by the fault number).

Source

Codes are listed as documented. Fault behaviour can vary by firmware revision, so confirm against the manual for your unit's series. Spotted an error? Tell us and we will correct it.

Related references

PowerFlex 40 part numbers these codes apply to

29 catalog numbers, 3 in stock now. Each links to stock, condition, repair pricing and series notes for that catalog number.

Disclaimer

Trademarks & Compatibility

All trademarks, service marks, trade names, brand names, and logos displayed on this website are the property of their respective owners. Any references to manufacturers, products, or brands are for identification and compatibility purposes only and do not imply any affiliation with, endorsement by, sponsorship from, or authorization by the respective trademark owners.

Independent Supplier

NJT Automation is an independent supplier of surplus, refurbished, and pre-owned industrial automation equipment. Unless expressly stated otherwise, NJT Automation is not an authorized distributor, dealer, representative, or affiliate of the original equipment manufacturer (OEM) for any products offered on this website.

Product Condition & Warranty

Products sold by NJT Automation may be surplus inventory, discontinued models, older series, or units with earlier manufacturing date codes than those currently available from the OEM or its authorized distribution network. As NJT Automation is not an authorized distributor, manufacturer warranties, support programs, and other OEM services may not apply. Any warranty provided is solely that of NJT Automation, where applicable.

Firmware & Software Licensing

Certain programmable logic controllers (PLCs), drives, HMIs, and other electronic products may require firmware to operate. While some products may include firmware, NJT Automation makes no representations or warranties regarding whether firmware is installed, the firmware version or revision level, its compatibility with your application, or its licensing status.

NJT Automation does not provide, obtain, transfer, or license firmware on behalf of customers. We make no representation regarding your ability or legal right to obtain, download, install, or use firmware from the OEM, its authorized distributors, or any other source. It is the customer's sole responsibility to ensure compliance with all applicable End User License Agreements (EULAs), software licenses, intellectual property rights, and other terms governing the acquisition, installation, and use of firmware.