Allen-Bradley 22B · Fault code reference
PowerFlex 40 Fault Codes
Every fault code a PowerFlex 40 reports on the drive's integral keypad display (F followed by the fault number), with what each one indicates, as documented in Rockwell Automation publication 22B-UM001.
22 codes · 22B-UM001 · 29 part numbers covered
PowerFlex 40 fault code list
| Code | Fault | What it indicates |
|---|---|---|
| F2 | Auxiliary Input | The auxiliary input interlock is open; check remote wiring. |
| F3 | Power Loss | Excessive DC bus voltage ripple: incoming phase loss, line imbalance or a blown input fuse. |
| F4 | UnderVoltage | DC bus voltage fell below the minimum value: low or interrupted incoming line. |
| F5 | OverVoltage | DC bus voltage exceeded the maximum value: high line, transients or a regenerative load. |
| F6 | Motor Stalled | The drive is unable to accelerate the motor; lengthen accel time or reduce load. |
| F7 | Motor Overload | Internal electronic motor overload trip. |
| F8 | Heatsink OvrTmp | Heatsink temperature exceeded the limit: blocked or dirty fins, high ambient or a failed fan. |
| F12 | HW OverCurrent | Output current exceeded the hardware current limit: excess load, boost setting or shorted motor leads. |
| F13 | Ground Fault | A current path to earth ground was detected at one or more output terminals. |
| F29 | Analog Input Loss | An analog input configured to fault on signal loss has lost its signal. |
| F33 | Auto Rstrt Tries | The drive used all programmed auto-restart attempts without clearing the fault. |
| F38 / F39 / F40 | Phase U / V / W to Gnd | A phase-to-ground fault was detected between the drive and motor in that phase. |
| F41 / F42 / F43 | Phase UV / UW / VW Short | Excessive current was detected between two output terminals. |
| F48 | Params Defaulted | The drive was commanded to write default values to EEPROM. |
| F63 | SW OverCurrent | The programmed software current trip level was exceeded. |
| F64 | Drive Overload | The drive rating of 150% for 1 minute or 200% for 3 seconds was exceeded. |
| F70 | Power Unit | A failure was detected in the drive power section. |
| F71 | Net Loss | The communication network faulted; check cabling and adapter settings. |
| F80 | SVC Autotune | The autotune function was cancelled or failed. |
| F81 | Comm Loss | The RS-485 (DSI) port stopped communicating. |
| F100 | Parameter Checksum | The parameter checksum does not match: reset to defaults and reprogram. |
| F122 | I/O Board Fail | A failure was detected in the drive control and I/O section. |
Is it a hardware fault?
Where the manual's only remedy for a code is to replace the unit or module, the code is pointing at a hardware fault inside that part, not at wiring, configuration or the application. Those are the faults NJT Automation repairs at component level. A repair is usually cheaper and faster than a replacement for an obsolete PowerFlex 40 unit; each part number below links to its stock, repair pricing and test videos.
Faults are read from the drive's integral keypad display (F followed by the fault number).
Source
- Rockwell Automation publication 22B-UM001, PowerFlex 40 Adjustable Frequency AC Drive User Manual
Codes are listed as documented. Fault behaviour can vary by firmware revision, so confirm against the manual for your unit's series. Spotted an error? Tell us and we will correct it.
Related references
PowerFlex 40 part numbers these codes apply to
29 catalog numbers, 3 in stock now. Each links to stock, condition, repair pricing and series notes for that catalog number.
- 22B-D2P3N1046 in stockPowerFlex 40 AC drive
- 22B-D4P0N1043 in stockPowerFlex 40 AC drive
- 22B-D024N1041 in stockPowerFlex 40 AC drive
- 22B-B012N104PowerFlex 40 AC drive
- 22B-B017N104PowerFlex 40 AC drive
- 22B-D001N100
- 22B-D001N101
- 22B-D001N102
- 22B-D001N103
- 22B-D001N104
- 22B-D002N103
- 22B-D002N104
- 22B-D004N102
- 22B-D004N103
- 22B-D004N104
- 22B-D4P0N101
- 22B-D4P0N102
- 22B-D4P0N103
- 22B-D006N102
- 22B-D006N103
- 22B-D006N104
- 22B-D6P0N104PowerFlex 40 AC drive
- 22B-D008N102
- 22B-D008N103
- 22B-D008N104
- 22B-D010N101
- 22B-D010N104PowerFlex 40 AC drive
- 22B-D012N104PowerFlex 40 AC drive
- 22B-D017N104PowerFlex 40 AC drive