Series comparison
SLC 500 Processor Series A vs B vs C (5/03, 5/04, 5/05)
On an SLC 500 processor the series letter tracks the operating system it shipped with. A later series runs a program written for an earlier one; an earlier series rejects a program that uses instructions from a newer OS. RSLogix 500 itself keys on catalog number and OS/FRN, not series.
At a glance
Operating system as shipped, by series
| Processor | Series A | Series B | Series C |
|---|---|---|---|
| SLC 5/03 (1747-L53x) | OS300 | OS301 | OS302 |
| SLC 5/04 (1747-L54x) | OS400 | OS401 | OS401 |
| SLC 5/05 (1747-L55x) | OS500, can be flashed to OS501; 10 Mbps Ethernet | OS501; 10 Mbps Ethernet | OS501; 10/100 Mbps Ethernet |
SLC 5/03 processors (1747-L53x)
Series A shipped with OS300, Series B with OS301 and Series C with OS302; earlier units take the 1747-OS302 upgrade cartridge.
Can one series replace another?
Same slot and wiring. A later series runs an earlier program; match or exceed the OS/FRN of the unit being replaced.
SLC 5/04 processors (1747-L54x)
Series A shipped with OS400, later series with OS401; the 1747-OS401 cartridge upgrades earlier units.
Can one series replace another?
Same slot and wiring. A later series runs an earlier program; a program that needs OS401 will not load on Series A.
SLC 5/05 processors (1747-L55x)
Series A shipped with OS500 and can be flashed to OS501; Series B and C ship with OS501. Only Series C hardware has the 10/100 Mbps Ethernet port; A and B run 10 Mbps half duplex.
Can one series replace another?
Same slot and wiring. A later series runs an earlier program; an earlier series rejects a program that uses newer OS/FRN features.
Sources and related references
Source: Rockwell Automation 1747-UM011. Confirm against the manual and the label on your unit; firmware and feature support can change between revisions of the same series.
Part numbers this applies to
8 catalog numbers, 5 in stock now. Each page shows the series NJT has in stock and has sold for that catalog number.