SLC 500 Processor Fault Codes
Every fault code a SLC 500 Processor reports on status word S:6 in RSLogix 500 (hexadecimal), with what each one indicates, as documented in Rockwell Automation publication 1747-RM001.
50 codes · 1747-RM001 · 12 part numbers covered
SLC 500 Processor fault code list
| Code | Fault | What it indicates |
|---|---|---|
| 0001 | NVRAM error | Processor memory was corrupted: noise, lightning, poor grounding or missing surge suppression on inductive loads. The default program is loaded. |
| 0002 | Unexpected hardware watchdog timeout | The processor reset unexpectedly; usually electrical noise or a failing processor. |
| 0003 | Memory module memory error | The memory module is corrupted. This can also occur when going to REM Run mode. |
| 0004 | Memory error in Run mode | Processor memory became corrupt while running. |
| 0007 | Memory module transfer failure | Transfer from the memory module failed; the module is corrupted. |
| 0008 | Internal software error | Unexpected software error, typically caused by noise or a hardware problem. |
| 0009 | Internal hardware error | Unexpected hardware error inside the processor. |
| 0010 | Processor revision too low | The processor does not meet the revision level the program requires. |
| 0011 | Program file 2 absent | Executable program file number 2 is missing: incompatible or corrupt program. |
| 0012 | Ladder program memory error | The ladder program has a memory integrity problem. |
| 0013 | Memory module absent | The required memory module is absent, or S:1/10 / S:1/11 is not set as the program requires. |
| 0014 | Internal file error | Processor data files are corrupted. |
| 0015 | Configuration file error | The I/O configuration file is corrupted. |
| 0016 | Startup protection after power loss | S:1/9 is set and power was lost while running; the processor waits for the fault routine to clear it. |
| 0017 | NVRAM / memory module mismatch | S:2/9 is set and the memory module program does not match the NVRAM program. |
| 0018 | Incompatible user program | Operating system type mismatch: the program was written for a different or newer processor. |
| 0019 | Duplicate label | A duplicate or missing LBL instruction was found in a subroutine. |
| 001F | Online edit integrity problem | Noise, communication loss or a power cycle occurred during an online editing session. |
| 0020 | Minor error at end of scan | A minor error bit in S:5 (lower byte) was set at the end of the scan, for example a math overflow. |
| 0021 | Remote expansion chassis power failure | An expansion I/O chassis lost power, or an over-voltage / over-current condition occurred. |
| 0022 | Watchdog scan time exceeded | The program scan took longer than the watchdog setpoint, or the program is caught in a loop. |
| 0023 | Invalid STI interrupt file | The STI interrupt file number is invalid or the subroutine does not exist. |
| 0024 | Invalid STI interval | The STI setpoint is greater than 2550 ms or negative. |
| 0025–0027 | Excessive stack depth / JSR calls | A JSR instruction is calling the STI, I/O interrupt or user fault routine file directly. |
| 0028 | Invalid startup-protection fault routine | The fault routine file number in the status file does not exist or is invalid. |
| 0029–002D | Indexed / indirect address error | An indexed or indirect address references outside its data file or data space. |
| 002E | Invalid DII input slot | The DII slot is empty or does not hold a discrete input module. |
| 002F | Invalid DII interrupt file | The DII interrupt file number is invalid or the subroutine does not exist. |
| 0030 | Subroutine nesting exceeded | Too many nested JSRs, or potentially recursive routines. |
| 0031 | Unsupported instruction | The processor type or series does not support an instruction in the program. |
| 0032 | Sequencer out of range | A sequencer length / position parameter points past the end of a data file. |
| 0033 | Bit shift / FIFO / LIFO out of range | The length parameter of an LFU, LFL, FFU, FFL, BSL or BSR instruction points past the end of a data file. |
| 0034 | Negative timer value | A negative timer accumulator or preset value was detected. |
| 0035 | TND / SVC / REF in interrupt routine | A TND, SVC or REF instruction is used inside an interrupt or user fault routine. |
| 0036 | Invalid PID parameter | An invalid value is being used for a PID instruction parameter. |
| 0038 | RET outside subroutine | A RET instruction resides in the main program file. |
| 003A | Write to protected file | An attempt was made to write to a constant / protected data file. |
| 003B | Firmware mismatch | Motherboard and daughter card firmware were not flash-upgraded as a pair. |
| 003C | STI watchdog timeout | The STI setpoint is set too low for the routine. |
| 005F | Invalid rack ID | Invalid rack setup or a problem with the rack. |
| xx50 | Chassis data error | Slot xx returned bad chassis data; usually noise or grounding. |
| xx51 | Stuck runtime error | A stuck I/O module in slot xx: noise on a discrete module or a fault on a specialty module. |
| xx52 | Module missing | The module configured for slot xx is missing or was removed. |
| xx53 | Unused slot has module | A slot declared unused contains a module, or a module reset itself. |
| xx54 | Wrong module type | The module in slot xx is a different type than configured. |
| xx55 | Wrong I/O count | The discrete module in slot xx has a different I/O count than configured. |
| xx56 | Chassis configuration error | The chassis configuration in the program does not match the hardware. |
| xx57–xx5E | Specialty module error | A specialty I/O module in slot xx faulted, timed out or has an invalid G / M0-M1 file configuration. |
| xx90–xx93 | Disabled-slot / ISR error | A specialty module in a disabled slot requested service or faulted, or its interrupt subroutine is invalid. |
| xx94 | Module inserted under power | A module was inserted under power in Run or Test mode, or reset itself. |
Is it a hardware fault?
Where the manual's only remedy for a code is to replace the unit or module, the code is pointing at a hardware fault inside that part, not at wiring, configuration or the application. Those are the faults NJT Automation repairs at component level. A repair is usually cheaper and faster than a replacement for an obsolete SLC 500 Processor unit; each part number below links to its stock, repair pricing and test videos.
Faults are read from status word S:6 in RSLogix 500 (hexadecimal).
Source
- Rockwell Automation publication 1747-RM001, SLC 500 Instruction Set Reference Manual
Codes are listed as documented. Fault behaviour can vary by firmware revision, so confirm against the manual for your unit's series. Spotted an error? Tell us and we will correct it.
Related references
SLC 500 Processor part numbers these codes apply to
12 catalog numbers, 5 in stock now. Each links to stock, condition, repair pricing and series notes for that catalog number.
- 1747-L5316 in stockSLC 5/03 PLC Processor
- 1747-L5421 in stockSLC 5/04 PLC Processor
- 1747-L5518 in stockSLC 5/05 PLC Processor
- 1747-L5526 in stockSLC 5/05 PLC Processor
- 1747-L5532 in stockSLC 5/05 PLC Processor
- 1747-L40CSLC 500 Fixed I/O Controller
- 1747-L511SLC 5/01 PLC Processor
- 1747-L514SLC 5/01 PLC Processor
- 1747-L524SLC 5/02 PLC Processor
- 1747-L532SLC 5/03 PLC Processor
- 1747-L541SLC 5/04 PLC Processor
- 1747-L543SLC 5/04 PLC Processor