Allen-Bradley 1746 · Fault code reference
SLC 500 I/O Module Fault Codes
Every fault code a SLC 500 I/O Module reports on the SLC processor's status word S:6 in RSLogix 500, where xx is the slot number this module occupies, with what each one indicates, as documented in Rockwell Automation publication 1747-RM001.
10 codes · 1747-RM001 · 23 part numbers covered
SLC 500 I/O Module fault code list
| Code | Fault | What it indicates |
|---|---|---|
| xx50 | Chassis data error | Slot xx returned bad chassis data; usually noise or grounding. |
| xx51 | Stuck runtime error | A stuck I/O module in slot xx: noise on a discrete module or a fault on a specialty module. |
| xx52 | Module missing | The module configured for slot xx is missing or was removed. |
| xx53 | Unused slot has module | A slot declared unused contains a module, or a module reset itself. |
| xx54 | Wrong module type | The module in slot xx is a different type than configured. |
| xx55 | Wrong I/O count | The discrete module in slot xx has a different I/O count than configured. |
| xx56 | Chassis configuration error | The chassis configuration in the program does not match the hardware. |
| xx57–xx5E | Specialty module error | A specialty I/O module in slot xx faulted, timed out or has an invalid G / M0-M1 file configuration. |
| xx90–xx93 | Disabled-slot / ISR error | A specialty module in a disabled slot requested service or faulted, or its interrupt subroutine is invalid. |
| xx94 | Module inserted under power | A module was inserted under power in Run or Test mode, or reset itself. |
Is it a hardware fault?
Where the manual's only remedy for a code is to replace the unit or module, the code is pointing at a hardware fault inside that part, not at wiring, configuration or the application. Those are the faults NJT Automation repairs at component level. A repair is usually cheaper and faster than a replacement for an obsolete SLC 500 I/O Module unit; each part number below links to its stock, repair pricing and test videos.
Faults are read from the SLC processor's status word S:6 in RSLogix 500, where xx is the slot number this module occupies.
Source
- Rockwell Automation publication 1747-RM001, SLC 500 Instruction Set Reference Manual
Codes are listed as documented. Fault behaviour can vary by firmware revision, so confirm against the manual for your unit's series. Spotted an error? Tell us and we will correct it.
Related references
SLC 500 I/O Module part numbers these codes apply to
23 catalog numbers, 1 in stock now. Each links to stock, condition, repair pricing and series notes for that catalog number.
- 1746-IV161 in stockSLC 500 digital input module
- 1746-FIO4VSLC 500 analog combination module
- 1746-IA8SLC 500 digital input module
- 1746-IA8K
- 1746-IA8KK
- 1746-IA16SLC 500 digital input module
- 1746-IA16-C
- 1746-IB16SLC 500 digital input module
- 1746-IO12SLC 500 digital combination module
- 1746-IV16K
- 1746-IV16KK
- 1746-IV32SLC 500 digital input module
- 1746-NI8SLC 500 analog input module
- 1746-NIO4ISLC 500 analog combination module
- 1746-NO4ISLC 500 analog output module
- 1746-NO8ISLC 500 analog output module
- 1746-NR4SLC 500 RTD input module
- 1746-NT8SLC 500 thermocouple input module
- 1746-OA16SLC 500 digital output module
- 1746-OB16SLC 500 digital output module
- 1746-OBP16SLC 500 digital output module
- 1746-OW16SLC 500 relay output module
- 1746-OX8SLC 500 relay output module