| Code | Fault | What it indicates |
|---|---|---|
| 0001 | NVRAM error | Program memory was corrupted (power loss during download, noise, failing battery) and the default program was loaded. |
| 0002 | Unexpected reset | The controller reset unexpectedly due to noise or an internal hardware failure; the default program is loaded. |
| 0003 | Memory module program corrupt | Memory module memory error; can also appear when going to Run mode. |
| 0004 | Memory integrity error | ROM or RAM became corrupt at power-up or during the background integrity check. |
| 0006 | Memory module hardware fault | The memory module hardware faulted or is incompatible with the operating system. |
| 0007 | Memory module transfer error | Failure during memory module transfer. |
| 0008 | Fatal internal software error | Unexpected software error; cycle power and reload the program. |
| 0009 | Fatal internal hardware error | Unexpected hardware error; cycle power and reload the program. |
| 000A | OS missing or corrupt | The operating system required for the user program is missing or corrupt. |
| 000B | Base hardware fault | The base hardware faulted or is incompatible with the operating system. |
| 0011 | Executable file 2 missing | Ladder file 2 is missing from the program. |
| 0012 | Ladder program error | The ladder program has a memory integrity problem. |
| 0015 | I/O configuration file error | The user program I/O configuration is invalid. |
| 0016 | Startup protection fault | The user fault routine ran at power-up and S:1/13 was not cleared. |
| 0017 | NVRAM / memory module mismatch | S:2/9 is set and the memory module program does not match the controller program. |
| 0018 | Memory module program incompatible with OS | The program stored in the memory module needs a newer operating system. |
| 001A | User program incompatible with OS | The user program is incompatible with the controller operating system. |
| 0020 | Minor error at end of scan | A minor fault bit (S:5 bits 0–7) was set at the end of the scan. |
| 0022 | Watchdog timer expired | The program scan time exceeded the watchdog timeout in S:3H. |
| 0023 | STI error | An error occurred in the STI configuration; see the STI function file. |
| 0028 | Invalid user fault routine | The fault routine number in S:29 is invalid or the routine does not exist. |
| 0029 | Indirect address outside data space | An indirect address reference is outside the entire data file space. |
| 002E | EII error | An error occurred in the EII configuration; see the EII function file. |
| 0030 | Subroutine nesting exceeds limit | JSR nesting exceeded the controller memory space. |
| 0031 | Unsupported instruction | The program contains an instruction this controller does not support. |
| 0032 | Sequencer outside data file space | An SQO / SQC / SQL length or position parameter references outside the data file space. |
| 0033 | Bit shift / FIFO / LIFO crossed data file | A BSL, BSR, FFL, FFU, LFL or LFU parameter references outside the data file space. |
| 0034 | Negative timer value | A negative value was loaded to a timer preset or accumulator. |
| 0035 | Illegal instruction in interrupt file | A TND, REF or SVC instruction is used in an interrupt subroutine. |
| 0036 | Invalid PID parameter | An invalid value is being used for a PID instruction parameter. |
| 0037 | HSC error | An error occurred in the high-speed counter configuration; see the HSC function file. |
| 003B | PTO error | An error occurred in the PTO instruction configuration. |
| 003C | PWM error | An error occurred in the PWM instruction configuration. |
| 003D | Invalid sequencer length / position | A sequencer length or position parameter is greater than 255. |
| 003E | Invalid bit shift or FIFO / LIFO parameter | A BSR / BSL length is greater than 2048, or an FFU / FFL / LFU / LFL length is out of range. |
| 003F | COP / CPW / FLL outside data file space | A COP, CPW or FLL length parameter references outside the data space. |
| 0042 | Invalid recipe number | Number of recipes specified is greater than 256. |
| 0044 | Invalid write to RTC function file | A write to the real-time clock function file contained invalid data. |
| 0050 | Controller type mismatch | The controller type selected in the program does not match the actual controller. |
| 0051 | Base type mismatch | The hardware base type selected in the program does not match the actual base. |
| 0052 | Minimum series error | The hardware minimum series in the program is newer than the actual hardware. |
| 0083 | Max I/O cables exceeded | Too many expansion I/O cables in the system. |
| 0084 | Max I/O power supplies exceeded | Too many expansion I/O power supplies in the system. |
| 0085 | Max I/O modules exceeded | Too many expansion I/O modules in the system. |
Is it a hardware fault?
Where the manual's only remedy for a code is to replace the unit or module, the code is pointing at a hardware fault inside that part, not at wiring, configuration or the application. Those are the faults NJT Automation repairs at component level. A repair is usually cheaper and faster than a replacement for an obsolete MicroLogix 1400 unit; each part number below links to its stock, repair pricing and test videos.
Faults are read from the controller LCD and status word S:6 in RSLogix 500 / RSLogix Micro (hexadecimal).
Source
- Rockwell Automation publication 1766-RM001, MicroLogix 1400 Programmable Controllers Instruction Set Reference Manual
Codes are listed as documented. Fault behaviour can vary by firmware revision, so confirm against the manual for your unit's series. Spotted an error? Tell us and we will correct it.
Related references
MicroLogix 1400 part numbers these codes apply to
6 catalog numbers, 4 in stock now. Each links to stock, condition, repair pricing and series notes for that catalog number.
- 1766-L32AWA1 in stockMicroLogix 1400 controller
- 1766-L32BWA1 in stockMicroLogix 1400 controller
- 1766-L32BWAA2 in stockMicroLogix 1400 controller
- 1766-L32BXB1 in stockMicroLogix 1400 controller
- 1766-L32AWAAMicroLogix 1400 controller
- 1766-L32BXBAMicroLogix 1400 controller