Allen-Bradley 1756 / 1769 / 5069 · Fault code reference

ControlLogix and CompactLogix Fault Codes

Every fault code a ControlLogix and CompactLogix reports on the Major Faults tab in Studio 5000 Logix Designer / RSLogix 5000 as Type:Code (T:C), with what each one indicates, as documented in Rockwell Automation publication 1756-RD001.

42 codes · 1756-RD001 · 138 part numbers covered

ControlLogix and CompactLogix fault code list

ControlLogix and CompactLogix fault codes
CodeFaultWhat it indicates
T01:C01Power-up faultPower was lost and restored while the controller was in RUN mode.
T01:C16Power-up faultI/O communications configuration fault detected at power-up.
T01:C40Power-up faultEnergy storage module or battery failed during the last power-down; retained data may be lost.
T01:C60Power-up faultNon-recoverable fault. The controller must be reflashed or returned for repair.
T01:C61Power-up faultNon-recoverable fault with saved diagnostic information.
T01:C62Power-up faultNon-recoverable fault with saved diagnostic information and stored user program.
T03:C16I/O faultAn I/O module connection failed on a module marked as required.
T03:C20I/O faultUnable to read ControlBus chassis information; the chassis may be bad.
T03:C21I/O faultUnable to read ControlBus chassis information; the chassis may be bad.
T03:C23I/O faultAt least one required connection was not established before going into RUN mode.
T04:C16Program faultUnknown instruction encountered.
T04:C20Program faultArray subscript too large, or CONTROL data type POS or LEN invalid.
T04:C21Program faultCONTROL data type LEN or POS less than 0.
T04:C24Program faultUnknown data type passed to a subroutine.
T04:C31Program faultJSR or RET did not pass as many parameters as expected.
T04:C34Program faultA timer instruction had a negative value for its PRE or ACC.
T04:C42Program faultJMP to a label that did not exist or was deleted.
T04:C82Program faultCould not re-enter an executing SFC routine.
T04:C83Program faultValue out of range.
T04:C84Program faultStack overflow: stack too small to perform the operation.
T04:C85Program faultInvalid routine type.
T04:C89Program faultTarget step does not exist in the specified routine.
T04:C90Program faultA safety instruction occurs outside a safety task.
T04:C91Program faultEquipment phase instruction cannot be called from a program.
T04:C94Program faultNesting limits exceeded.
T04:C990–C999Program faultUser-defined major fault raised by the application.
T06:C01Watchdog faultTask watchdog expired: an infinite loop, an over-complex program or a higher-priority task starved the task.
T07:C40Nonvolatile faultStore to nonvolatile memory (CompactFlash / SD) failed.
T07:C41Nonvolatile faultLoad from nonvolatile memory failed: controller type mismatch.
T07:C42Nonvolatile faultLoad from nonvolatile memory failed: controller revision mismatch.
T07:C43Nonvolatile faultLoad from nonvolatile memory failed: bad checksum.
T07:C44Nonvolatile faultFailed to restore processor memory.
T07:C50Nonvolatile faultSecurity certificate invalid.
T08:C01Mode change faultMode change inhibited because a download is in progress.
T11:C01Motion faultActual position of the axis exceeded the positive overtravel limit.
T11:C02Motion faultActual position of the axis exceeded the negative overtravel limit.
T11:C03Motion faultActual position exceeded the position error tolerance.
T11:C04Motion faultEncoder channel A, B or Z connection failed.
T11:C05Motion faultEncoder noise event detected, or encoder signals not in quadrature.
T11:C06Motion faultDrive fault reported by the servo drive.
T11:C07Motion faultSynchronous connection to the servo module failed.
T11:C08Motion faultHardware failure in the servo module.

Is it a hardware fault?

Where the manual's only remedy for a code is to replace the unit or module, the code is pointing at a hardware fault inside that part, not at wiring, configuration or the application. Those are the faults NJT Automation repairs at component level. A repair is usually cheaper and faster than a replacement for an obsolete ControlLogix and CompactLogix unit; each part number below links to its stock, repair pricing and test videos.

Faults are read from the Major Faults tab in Studio 5000 Logix Designer / RSLogix 5000 as Type:Code (T:C).

Source

  • Rockwell Automation publication 1756-RD001, Logix 5000 Controller and I/O Fault Codes

Codes are listed as documented. Fault behaviour can vary by firmware revision, so confirm against the manual for your unit's series. Spotted an error? Tell us and we will correct it.

Related references

ControlLogix and CompactLogix part numbers these codes apply to

138 catalog numbers, 32 in stock now. Each links to stock, condition, repair pricing and series notes for that catalog number.

Disclaimer

Trademarks & Compatibility

All trademarks, service marks, trade names, brand names, and logos displayed on this website are the property of their respective owners. Any references to manufacturers, products, or brands are for identification and compatibility purposes only and do not imply any affiliation with, endorsement by, sponsorship from, or authorization by the respective trademark owners.

Independent Supplier

NJT Automation is an independent supplier of surplus, refurbished, and pre-owned industrial automation equipment. Unless expressly stated otherwise, NJT Automation is not an authorized distributor, dealer, representative, or affiliate of the original equipment manufacturer (OEM) for any products offered on this website.

Product Condition & Warranty

Products sold by NJT Automation may be surplus inventory, discontinued models, older series, or units with earlier manufacturing date codes than those currently available from the OEM or its authorized distribution network. As NJT Automation is not an authorized distributor, manufacturer warranties, support programs, and other OEM services may not apply. Any warranty provided is solely that of NJT Automation, where applicable.

Firmware & Software Licensing

Certain programmable logic controllers (PLCs), drives, HMIs, and other electronic products may require firmware to operate. While some products may include firmware, NJT Automation makes no representations or warranties regarding whether firmware is installed, the firmware version or revision level, its compatibility with your application, or its licensing status.

NJT Automation does not provide, obtain, transfer, or license firmware on behalf of customers. We make no representation regarding your ability or legal right to obtain, download, install, or use firmware from the OEM, its authorized distributors, or any other source. It is the customer's sole responsibility to ensure compliance with all applicable End User License Agreements (EULAs), software licenses, intellectual property rights, and other terms governing the acquisition, installation, and use of firmware.