Series comparison
ControlLogix Controller Series Differences: L1, L55, L6x, L7x and 5580
Studio 5000 Logix Designer (and RSLogix 5000 before it) keys a controller on its catalog number and firmware revision, not its series letter. The series still matters on the bench: it decides which battery or energy-storage module the controller takes, and on the 5580 family it sets the firmware range.
At a glance
Controller series at a glance
| Controller | Series | What differs |
|---|---|---|
| 1756-L1, 1756-L55 | All | 1756-BA1 battery. On the L55 the memory board (1756-M1x / M2x) is part of the catalog number. |
| 1756-L61 to 1756-L65 | Series A | 1756-BA1 battery. Same firmware files as Series B. |
| 1756-L61 to 1756-L65 | Series B | 1756-BA2 battery. Same firmware files as Series A. |
| 1756-L71 to 1756-L75 | All | No battery: 1756-ESMCAP energy-storage module and a 1784-SD1 / SD2 card. |
| 1756-L81E to 1756-L85E | Series A | Runs the early 5580 firmware revisions (28 to 30) as well as later ones. |
| 1756-L81E to 1756-L85E | Series B | Firmware revision 31.011 or later only. |
ControlLogix 1756-L1 and L55 controllers
All series use the 1756-BA1 battery; on the L55 the memory board (1756-M1x/M2x) is part of the catalog number.
Can one series replace another?
RSLogix 5000 keys on catalog number and firmware revision, not series; flash the replacement to the project's revision.
ControlLogix 1756-L61 to L65 controllers
Series A uses the 1756-BA1 battery; Series B uses the 1756-BA2. Firmware files are the same for both.
Can one series replace another?
Studio 5000 keys on catalog number and firmware revision, not series; fit the correct battery for the series.
ControlLogix 1756-L71 to L75 controllers
All series use the 1756-ESMCAP energy-storage module and a 1784-SD1 / SD2 card; no battery.
Can one series replace another?
Studio 5000 keys on catalog number and firmware revision, not series.
ControlLogix and GuardLogix 5580 controllers (1756-L8xE)
Series B controllers run firmware revision 31.011 or later; Series A units also run the earlier 5580 revisions (28 to 30).
Every series needs a Series B or Series C 1756 chassis (Series B derated to 50 °C ambient); 5580 controllers do not work in a Series A chassis.
Can one series replace another?
Studio 5000 keys on catalog number and firmware revision, not series. Fitting a Series B into a project on revision 28 to 30 means upgrading the project to 31 or later first.
Sources and related references
Source: Rockwell Automation 1756-UM001; Rockwell Automation 1756-UM543, 1756-TD001, Product Compatibility and Download Center. Confirm against the manual and the label on your unit; firmware and feature support can change between revisions of the same series.
Part numbers this applies to
49 catalog numbers, 13 in stock now. Each page shows the series NJT has in stock and has sold for that catalog number.
- 1756-L712 in stockControlLogix 5570 controller
- 1756-L72S1 in stockGuardLogix 5570 safety controller
- 1756-L751 in stockControlLogix 5570 controller
- 1756-L81E5 in stockControlLogix 5580 controller
- 1756-L81ES2 in stockGuardLogix 5580 safety controller
- 1756-L82E8 in stockControlLogix 5580 controller
- 1756-L82EK1 in stockControlLogix 5580 controller
- 1756-L82ES1 in stockGuardLogix 5580 safety controller
- 1756-L83E3 in stockControlLogix 5580 controller
- 1756-L83EP3 in stockControlLogix 5580 Process controller
- 1756-L83ES1 in stockGuardLogix 5580 safety controller
- 1756-L84E1 in stockControlLogix 5580 controller
- 1756-L84ES2 in stockGuardLogix 5580 safety controller
- 1756-L55M12ControlLogix 5555 controller
- 1756-L55M13ControlLogix 5555 controller
- 1756-L55M14ControlLogix 5555 controller
- 1756-L55M16ControlLogix 5555 controller
- 1756-L55M22ControlLogix 5555 controller
- 1756-L55M23ControlLogix 5555 controller
- 1756-L55M24ControlLogix 5555 controller
- 1756-L55M26
- 1756-L61ControlLogix 5560 controller
- 1756-L61SGuardLogix 5560 safety controller
- 1756-L61SE
- 1756-L61SEK
- 1756-L62SGuardLogix 5560 safety controller
- 1756-L63ControlLogix 5560 controller
- 1756-L63KControlLogix 5560 controller
- 1756-L64ControlLogix 5560 controller
- 1756-L64/BControlLogix 5560 controller
- 1756-L71KControlLogix 5570 controller
- 1756-L71KDK
- 1756-L71SGuardLogix 5570 safety controller
- 1756-L71SKGuardLogix 5570 safety controller
- 1756-L72ControlLogix 5570 controller
- 1756-L72KKControlLogix 5570 controller
- 1756-L73ControlLogix 5570 controller
- 1756-L73SGuardLogix 5570 safety controller
- 1756-L73XTControlLogix 5570 controller
- 1756-L74ControlLogix 5570 controller
- 1756-L74KControlLogix 5570 controller
- 1756-L74KKControlLogix 5570 controller
- 1756-L75KControlLogix 5570 controller
- 1756-L75KKControlLogix 5570 controller
- 1756-L75SP
- 1756-L81ESKGuardLogix 5580 safety controller
- 1756-L82ES/BGuardLogix 5580 safety controller
- 1756-L85EControlLogix 5580 controller
- 1756-L85EPControlLogix 5580 Process controller